Date:05-14-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:3900759SYSTEM NAME:TURNER CUT RESORTCOUNTY:SAN JOAQUIN 
SOURCE NO.:All SourcesSOURCE NAME:N/ASOURCE CLASS:N/ASTATUS:N/A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA3900759_003_003 SECONDARY/GP-202308 1928 ALKALINITY, BICARBONATE 200.000 MG/L 08-17-2020 36 2023/08 DUE NOW
CA3900759_003_003 SECONDARY/GP-202308 1919 CALCIUM 40.000 MG/L 08-17-2020 36 2023/08 DUE NOW
CA3900759_003_003 SECONDARY/GP-202308 1929 ALKALINITY, CARBONATE < 10.000 MG/L 08-17-2020 36 2023/08 DUE NOW
CA3900759_003_003 SECONDARY/GP-202308 1017 CHLORIDE 235.000 MG/L 500 08-17-2020 36 2023/08 DUE NOW
CA3900759_003_003 SECONDARY/GP-202308 1022 COPPER, FREE < 50.000 UG/L 1000 50 08-17-2020 36 2023/08 DUE NOW
CA3900759_003_003 SECONDARY/GP-202308 2905 FOAMING AGENTS (SURFACTANTS) < 0.100 MG/L .5 08-17-2020 36 2023/08 DUE NOW
CA3900759_003_003 SECONDARY/GP-202308 1915 HARDNESS, TOTAL (AS CACO3) 203.000 MG/L 08-17-2020 36 2023/08 DUE NOW
CA3900759_003_003 SECONDARY/GP-202308 1021 HYDROXIDE AS CALCIUM CARBONATE < 10.000 MG/L 08-17-2020 36 2023/08 DUE NOW
CA3900759_003_003 SECONDARY/GP-202409 1028 IRON 16500.000 30.000 UG/L 300 100 09-20-2023 12 2024/09
CA3900759_003_003 SECONDARY/GP-202308 1031 MAGNESIUM 25.000 MG/L 08-17-2020 36 2023/08 DUE NOW
CA3900759_003_003 SECONDARY/GP-202409 1032 MANGANESE 840.000 10.000 UG/L 50 20 09-20-2023 12 2024/09
CA3900759_003_003 SECONDARY/GP-202308 1925 PH 7.300 pH 08-17-2020 36 2023/08 DUE NOW
CA3900759_003_003 SECONDARY/GP-null 1050 SILVER UG/L 100 10 36 DUE NOW
CA3900759_003_003 SECONDARY/GP-202308 1052 SODIUM 139.000 MG/L 08-17-2020 36 2023/08 DUE NOW
CA3900759_003_003 SECONDARY/GP-202308 1064 CONDUCTIVITY @ 25 C UMHOS/CM 1220.000 UMHO/CM 1600 08-17-2020 36 2023/08 DUE NOW
CA3900759_003_003 SECONDARY/GP-202308 1055 SULFATE 2.900 0.500 MG/L 500 .5 08-17-2020 36 2023/08 DUE NOW
CA3900759_003_003 SECONDARY/GP-202308 1930 TDS 680.000 MG/L 1000 08-17-2020 36 2023/08 DUE NOW
CA3900759_003_003 SECONDARY/GP-null 0100 TURBIDITY NTU 5 .1 36 DUE NOW
CA3900759_003_003 SECONDARY/GP-202308 1095 ZINC < 50.000 UG/L 5000 50 08-17-2020 36 2023/08 DUE NOW
CA3900759_003_003 NITRATE/NITRITE-202404 1040 NITRATE 0.900 0.400 MG/L 10 .4 04-11-2023 12 2024/04 DUE NOW
CA3900759_003_003 NITRATE/NITRITE-202604 1041 NITRITE < 0.400 MG/L 1 .4 04-11-2023 36 2026/04
CA3900759_009_009 REGULATED SOC-null 2414 1,2,3-TRICHLOROPROPANE UG/L 0.005 3 DUE NOW
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.